Pressure Levels

Pressure on suction and discharge openings for compressor also affect the load. The more pressure difference, the less power. When considered individually, the suction pressure has a greater impact on compressor capacity than the discharge pressure. In a comfort air conditioning system under normal operating conditions, differential pressure, which causes 1F reduce the amount of saturated refrigerant temperature at the compressor suction reduces its capacity is about 2%. On the other hand, the increase in pressure at the compressor discharge, which results 1F increase the saturation temperature leads only 1% decrease in productivity of the compressor.

Compressor suction pressures affect devices that control the performance of the compressor, for instance, cruise control, cylinder unloading, Cycling multiple compressors. At a given load, reduction of compressor output methods, as a rule, increase the suction pressure. Condenser pressure, control techniques affect the discharge pressure of the compressor. On a given workload, head pressure tends to increase of discharge pressure...

 
Thanks ->



Chiller Direct refrigeration system External equalizer Forced lubrication method High side float valve Hot air furnace wiring diagram Low pressure chillers Multi stage refrigeration system Potential relay and current relay R404a wiki R407c vs r134a Single screw compressor Two stage cascade refrigeration system