The Relationship Suction Line

When designing the suction line, the following important considerations should be observed:
  • The line shall have sufficient capacity to prevent any significant pressure drop at full load.
  • In multiple-element installations, all suction line should be reduced to a common collector to the compressor.
  • The difference in pressure between each compressor and the main suction line must be the same to ensure proportional amount of refrigerant for each compressor, as well as the timely return of oil for each compressor.
  • Equal pipe lengths, sizes, and spacing must be provided.
  • All collectors must be on the same level.
  • Inlet and outlet pipes should be staggered.
  • Never connect the branch to cross or tee.
  • In the common collector must have a size equal to the sum of the squares of the individual suction.
  • Suction pipe must be designed to prevent draining the compressor during shutdown cooling system.
..
 
Thanks ->



Capillary tube Cascade refrigeration system Chiller tube bundle repair Difference between fouling and scaling Dry expansion evaporator Effects of freezing on microorganisms Flooded evaporator Forced lubrication system wiki Heat of respiration Maltimitter phesh cheking Open drive compressor Pressure enthalpy diagram ammonia Shell and tube condenser