Lithium bromide water refrigeration cycle control - Lithium bromide absorption Capacity control

Technical information Chillers Capacity Control. Lithium Bromide - Water Absorption Chillers

Capacity Management. Lithium Bromide Absorption Chillers Water

One Effect Absorption chillers about 8C have an efficiency of about 0.5 to 0.6, EER is about 2.1 and Specific steam Consumption is about 8.75 kg/hour/TR, on the vapour pressure of 3 bar or below.

Double-Effect Absorption chillers about 8with the COP in the range from 1 to 1.2, EER in the range of 3.5-4 Btu/hr/W and Specific Steam Consumption in the range of 4.5-5.25 kg/hour/TR, vapor pressure from 8 to 8.5 bar. In the case of shot straight double-effect absorption chillers, the specific Fuel Consumption is likely to be about 0.35 m3/h/TR natural gas, or approximately 0.30 kg/h/TR fuel oil.

Triple-Effect Absorption chillers are implemented cooling international majors and told the COP of 1.6 i.e. EER more than 5. The steam consumption is likely to be about 2.3 kg/hour/TR...

 
Thanks ->



Advantages of bimetallic thermometer Air draft Basic furnace wiring diagram Capillary tube restrictor Crystallization in vapour absorption system Hcfc 22 Hot gas bypass Humidification and dehumidification wiki Modified splash lubrication system Overload protector Strainer drier Thermostatic expansion valve Two stage vacuum pump Wikipedia