Technical information Chillers How to detect: Condenser volume is too small

How to determine: Capacitor volume is too small

  • Specific to the chillers and heat pumps without liquid receiver with comparatively higher evaporator of the internal volume
  • In nominal terms, the condensing pressure and hypothermia may be normal
  • At low loads and low temperatures refrigerant boiling point more accumulates in the condenser, increase condensing temperature and subcooling, and in case of overload
  • Check the evaporator and condenser internal volumes
  • Consider installing a liquid receiver
How to determine: Oil condenser
  • Specific to the chillers and heat pumps without liquid receiver
  • Low superheat suction gas and short running times to increase the amount of oil coming out of the compressor
  • Compressor oil charge may be more than capacitor internal volume
  • For collection of oil in the capacitor reduces the size of the condensation surface. This will increase the temperature of condensation
  • Check the oil level in the compressor, if possible.

    Check the compressor running times and suction gas superheat
How to determine: non-condensable gases
  • Non-condensable gases have the same effect as excessive. Condensing pressure will rise and will not be freezing temperatures.
  • Pressure gauge can sometimes vibrate because of non-condensable gases
  • Non-condensable gases will collect in the top of the condenser, which makes it the best place to purge system

How to determine: the Dirt in the water capacitor

  • Of admixtures in water or in brine side may cause clogging or even block some water channels. This will increase pressure condensing
  • Capacitor can be cleaned by pumping water in the opposite direction compared to the normal operation. Cleaning agents can also be used
  • Recommended filters used for plate heat exchangers
How to determine: the Air in the water side of conden
  • The air in the direction of the condenser water heat transfer impai
  • The air in the circulation pump will reduce the water or brine flow
  • In addition to increasing the condensation temperature, air tours can lead characteristic noise, which will help to identify the cause of the problem
  • Verify that the expansion tank (A) is used on the discharge side of the circulating pump and pressure inside the tank properly
How to determine: High loads from the suction side
  • On a hot day with high humidity, download refrigerant from the system of air conditioning may exceed refrigerant cooler power of water
  • If the expansion valve (A) does not have the MOP function, the suction pressure (B) will be high. Refrigerant capacity will increase causing a high load on the condenser and the high condensing temperature (C)
Possible causes for the low condensing pressure
  • Condenser water flow too high
  • Water inlet temperature too low
  • Defective valves of the compressor
..
 
Thanks ->



Advantages of bimetallic thermometer Air draft Basic furnace wiring diagram Capillary tube restrictor Crystallization in vapour absorption system Hcfc 22 Hot gas bypass Humidification and dehumidification wiki Modified splash lubrication system Overload protector Refrigerant distributors Refrigerator compressor oil change Two stage vacuum pump Wikipedia