Technical information Chillers How to detect: Insufficient subcooling

How to determine: Lack of hypothermia

  • Not enough hypothermia, blocked filter-drier, a bend in the liquid line, a small solenoid valve and others, can cause outbreaks of gas in the liquid line, which reduces the bandwidth expansion valve
  • Flash gas is often causes sound hunting, which can be seen in the suction pressure manometer
  • Bubbles, which can be observed from the sight glass, if it is installed just before expansion valve
  • It is also possible to use electronic sight glass, such as TIFF-4000A to determine the state of the refrigerant

How to determine: the Dirt in the evaporator

  • Impurities on the water side can lead to fouling and even block some of the waterways.
  • Fouling will reduce the pressure boil and, thus, system capacity
  • Blocked water channels are very harmful for TEV operations because of the refrigerant drops can flow through the evaporator.
  • The evaporator can be cleaned by pumping water in the opposite direction compared to the normal operation.

    Cleaning agents can also be used.
  • Recommended filters to be used in front of the plate heat exchangers

How to determine: a Partial freeze

  • There is a risk of freezing, when other refrigerants R407C and high temperature are used glide
  • Although boiling temperature is above 0 C temperature at the inlet of the evaporator can be below 0 C
  • Even a partial freeze will reduce refrigerant capacity and increase the risk evaporator breakdown
  • Risk can be estimated by drawing cycle as log p (h)schema
  • In brine temperature measurement systems freezing using qualitative tools or simply place the sample in a frozen state, and attention to its melting/freezing points

How to determine: the Uneven distribution of liquid

  • Although the water flow and temperature depending on the choice of the program boiling point below, and overheating higher than it should be
  • The reason may be uneven distribution of the liquid inside the evaporator
  • Carefully remove the insulation from the evaporator side. Measure the surface temperature at many points with responsive thermometer
  • Temperature variations on a horizontal plane will be uneven liquid (water or) distribution inside the evaporator
..
 
Thanks ->



Application of refrigeration in chemical industry Approach temperature Carbon steel pipe fitting Circuit breaker Condenser Capacity Contact freezing Copper pipe sizes inches to mm Finned tube evaporator High side of a refrigeration system Oil separator in refrigeration cycle Refrigeration compressor Capacity control Refrigeration cycle Static condenser