Vacuum pump

The vacuum pump should be capable of quickly bringing the system pressure is about 0.05 mbar. Pump capacity, for example. 20 l/min Effective evacuation requires large-diameter pipes. Therefore evacuated via "Schroeder" valves is not recommended. Use "Quick Connector for compressors with the process tube or use the connectors at the compressor suction and possibly discharge valves. Valve must be in the middle position.

Vacuum hoses

Vacuum hoses and tubes should be as short as possible and sufficiently large diameter. As a rule, normal 1/4" hoses, not more than 1 m in length can be used. Evacuate in two stages with the refrigerant flushing between. The evacuation process, flushing, and charging described below.

Check the vacuum pump and hoses

  • Mount charging hoses between charging Board and the compressor. Disabling the connection between charging hoses and compressor.
  • Start the pump and let him suck blood pressure down, to the extent possible.
  • Disconnect the pump from the rest of the system.
  • Stop the pump.
  • Readings and record the pressure of the vacuum gauge. Pressure shall be not more than 0.05 mbar.
  • Make sure that the vacuum can be saved. If not, replace the charging hoses and/or leaking faucets and/or vacuum oil in the vacuum pump.
..
 
Thanks ->



Air standard refrigeration cycle Cartridge fuse diagram Condenser water regulating valve Double tube condenser High pressure float valve Hot gas muffler Open air refrigeration cycle Plate surface evaporator Pressurestats sense Solenoid valve Specific volume of refrigerant T. H. diagram Types of evaporator