Dryer Cycle

Drier removes water and non-condensable gases. This indicates any water leak in the refrigerant (see # 6 in Fig. 8-11).

This system contains refrigerant condensing coil and Commerce, the water drain valve, purging valve, pressure gauge, float valve refrigerant and refrigerant.

Desiccant-line fence constantly raises the refrigerant vapor and contaminants, if any, from the condenser. Vapor condenses into liquid desiccant condensing coil. Water, if present, disconnects, and floats on the surface of the liquid refrigerant. The water level can be observed through the sight glass.

Water can be withdrawn manually on water drain valve. Air. and other non-condensable gases collect in the top of the desiccant condensation chamber. Drier gage indicates the presence of air or other gases through the increase in pressure. These gases can be manually out through the purge valve.

Float valve maintains the refrigerant fluid level and pressure required for refrigerant condensing action. Purified refrigerant is returned to the refrigerator dryer float chamber.

..

 
Thanks ->



Capillary tube Cascade refrigeration system Chiller tube bundle repair Difference between fouling and scaling Effects of freezing on microorganisms Flash intercooler Flooded evaporator Forced lubrication system wiki Heat of respiration Maltimitter phesh cheking Pressure enthalpy diagram ammonia Psc compressor Shell and tube condenser